MKPPKPMKCPKCCalibration procedure0831106 Rev.0
2Calibration procedure for MKP - PKPINSTRUMENT CALIBRATIONPROCEDURES1 GENERAL GUIDELINES FOR CALIBRATIONFor an accurate calibration it is necessary to
3Calibration procedure for MKP - PKP2.4 IN CT / FEEDBACK SELECTIONThis instrument can use the "IN CT" input or the "Feedback" i
4Calibration procedure for MKP - PKP1.2) "Hr" - FINAL SCALE VALUEThe upper display will show "ñ.I.tc", the lower display will show
5Calibration procedure for MKP - PKPc) Set the calibrator to 275.00 Ω. The read-out must be "∀∀∀∀∀. 2 2166" + 10 counts.d) Push FUNC pus
6Calibration procedure for MKP - PKPthe instrument read-out (in counts).Instrument readout (in counts) = input value10 (V)•30000c) Push FUNC pushbu
7Calibration procedure for MKP - PKP9.3) "∀.∀.∀.∀.∀." - 10 V AUXILIARY INPUT CHECKThe lower and the middle display show "∀∀∀∀∀."
8Calibration procedure for MKP - PKP12.2) "Hr" - FINAL SCALE VALUEThe upper display will show "O5.ñA", the lower display will show
9Calibration procedure for MKP - PKP